The image displayed does not reflect the exact machine specifications, including attachments represented in the image on this machine.

C18 Generator Set

Caterpillar is leading the power generation marketplace with Power Solutions engineered to deliver unmatched flexibility, expandability, reliability, and cost-effectiveness.

Standby Rating
605/660/715/780/850 kVA
Prime Power Rating
550/600/650/706/770/600 kVA
Emissions/Fuel Strategy
China Non-Road Stage III Certified / Non-Certified Emissions
Voltage
380 to 415 Volts
Frequency
50 Hz
Speed
1500 rpm
Duty Cycle
Standby, Prime
Engine Model
C18 ATAAC, I-6, 4-Stroke Water-Cooled Diesel
Bore
5.71in
Stroke
7.2in
Displacement
1106.36in³
Compression Ratio
14.5:1
Aspiration
Air to Air Aftercooled
Fuel System
Electronic unit injection
Governor Type
Ademâ„¢A4
Length – Maximum
162.4in
Width – Maximum
78.3in
Height – Maximum
75in
  • Air Inlet System
    • Light duty air cleaner
  • Air Inlet
    • Air cleaner
  • Control System
    • GCCP 1.2
  • Exhaust
    • Exhaust flange outlet
  • Cooling
    • Coolant drain line with valve
    • Caterpillar extended life coolant
    • Fan drive, battery charging alternator drive
    • Radiator and cooling fan with guard
  • Exhaust System
    • Stainless steel exhaust flex gaskets, raincap and SAE exhaust flange for customer use – shipped loose
  • Fuel
    • Secondary fuel filters
    • Fuel priming pump
    • Primary fuel filter with integral water separator
  • Generator
    • IP23 Protection
    • Load adjustment module provides engine relief upon load impact and improves load acceptance and recovery time
    • Matched to the performance and output characteristics of Cat engines
  • Generator And Attachments
    • Segregated low voltage (AC/DC) wiring panel
    • Integrated voltage regulator (IVR)
    • Mandatory option circuit breaker, IEC, 3 pole, mounted in power centre
    • Power center, IP22
    • Matched to the performance and output characteristics of Cat engines
  • Power Termination
    • Busbar
  • Governing System
    • Cat electronic governor (ADEM A4)
  • Control Panel
    • GCCP Genset Controller
  • Lube System
    • Lubricating oil
    • Oil drain valves
  • Mounting
    • Rubber vibration isolators
  • Mounting System
    • Captive linear vibration isolators between base and engine-generator. includes lifting provisions and termination points for coolant and lube oil drain lines
  • Starting/charging
    • 24 Volt battery with rack and cables
  • General
    • Engine and alternator pre-paint, Caterpillar yellow
  • Telematics
    • Cat® Product Link™ PL444 cellular
  • Exhaust
    • Industrial, residential, critical mufflers
  • Air Inlet System
    • Dual element air cleaner
    • Single element air cleaner
  • Circuit Breakers
    • 3 Pole (IEC-100% rated) Circuit breakers – Motorised
    • 4 Pole (IEC-100% rated) Circuit breakers – Motorised
    • Circuit breaker (IEC) Auxiliary contacts
    • Padlockable circuit breaker device
    • 3 Pole (IEC-100% rated) Circuit breakers – Package mounted
    • 4 Pole (IEC-100% rated) Circuit breakers – Package mounted
    • Power terminal strip
    • Shunt trip for IEC breaker
  • Generator
    • Anti-condensation heater
    • Oversize and premium generators
  • Power Termination
    • Circuit breakers, IEC compliant
    • Circuit breakers, UL listed
  • Control Panels
    • Local & remote annunciator modules
    • Load share module
    • Remote monitoring software
    • Digital I/O module
  • Control System
    • Oil temperature displays
    • GCCP 1.4
    • Local alarm modules
    • Remote annunciator module
    • Local alarm horn
  • Cooling System
    • Low coolant temperature alarm
    • Radiator duct flange
  • Starting/charging
    • Oversize batteries
    • Jacket water heater
    • Battery chargers
    • Heavy duty starting system
    • Charging alternator
  • Enclosures
    • Sound attenuated enclosures
  • Exhaust System
    • Manifold and turbocharger guards
    • Engine mounted muffler
    • 8 and 10 inch elbow kits
    • 8 and 10 inch GP flanges
    • 10, 25 and 35 end in / end outmufflers
  • Fuel System
    • Optional BS799 Compliant Integral – Dual wall fuel tank base
    • Integral duall wall tank
    • Skid base
  • Generator And Attachments
    • LC frame generator
    • Permanent magnet excitation (PMG)
    • Space heaters
    • Ingress protection
    • LC frame CIP generator
  • General
    • Enclosures: Sound attenuated, weather protective
    • EU Certificate of Conformance (CE)
    • Integral & sub-base UL listed dual wall fuel tanks
    • Narrow, wide or skid base
    • EEC Declaration of Conformity
    • CSA Certification
    • Sound attenuated, weather protective or high ambient weather protective enclosure
    • Single or dual wall sub-base fuel tanks
  • Lube System
    • Manual sump pump
  • Starting And Charging
    • Jacket water heaters
    • 5 Amp Battery charger
    • Battery disconnect switch